AN ADVANCED FAULT DATA/INFORMATION PRESENTATION IN POWER SYSTEMS
Ozgur Gonen Noah Badayos
Mladen Kezunovic Biljana Matic Cuka
Visualization sciences Electrical and Computer
Electrical and Computer Electrical and Computer
Engineering
Engineering Engineering
Texas A&M University Texas A&M University Texas A&M University Texas A&M University
College Station, TX, College Station, TX,
College Station, TX, College Station,TX, 77840,
77840,USA 77840,USA
77840,USA USA
*****@***.****.*** ********@****.***
*******@***.****.*** *******@***.****.***
and computed information developed for various analysis
Abstract
applications and different utility groups.
To help make the power system more reliable huge
amount of data generated from different Intelligent The paper starts with providing background on fault
Electronic Devices (IEDs) located in substation of power analysis and IED data. The goal and implementation of
system should be collected, analysed and displayed. Easy some automated analysis applications are discussed next.
way of accessing and viewing recorded data or information The needs for presentation of field recorded data and
obtained through automated analysis is commonly lacking information obtained from automated analysis is outlined
in the existing power systems. Nowadays data and related and some implementation examples are discussed in the
information presentation is one of the most important following sections. Conclusion, Acknowledgement and
requirements in power engineering. Many users find that References are given at the end.
their work is more efficient when using versatile
data/information presentation software. The emphasis in this 2 IED DATA USED FOR FAULT ANALYSIS
paper is on implementing user-friendly, device independent
The main purpose of the fault analysis in the context of
data/information presentation with ability for remote access
this paper is to precisely determine spot on the transmission
too.
line where fault occurred and evaluate performance of the
equipment involved in fault clearing. Such analysis can
1 INTRODUCTION
provide information like fault type, confirmation whether a
This paper focuses on specific class of mostly software fault has in fact occurred, assessment of the accuracy of the
solutions in power systems, namely the ones related to fault location algorithms embedded in relays, performance
automated fault analysis for monitoring, maintenance and of the switching elements (circuit breakers) responsible for
control applications. This class of solutions collects data isolating faults, etc [4]. After a fault in power system takes
from Intelligent Electronic Devices (IEDs) in substations, place automatic actions of controllers responsible for fault
organizes it in appropriate databases, and in newer detection and classification (protective relays) and related
applications processes the data automatically to extract switching equipment (circuit breaker) status is immediately
information relevant to different utility groups such as seen by an operator in the control center who will take note
operators, protection engineers, and maintenance personnel. of the fault event and inform other staff like protection
group or maintenance [5]. The consequences of mentioned
The approach for automated collection and analysis of events are reconstructed from data collected by recording
IED data has been offered in the past by several vendors of devices located in substations, and the views of the
the solutions for power industry [1]. However, most of the data/information explaining the events and consequences
focus in the past was on implementing data collection and are displayed in the staff offices that are quite remote from
integration, which are only the first step towards analysis substations. Various groups, such as protection engineers,
automation [2]. Automated analysis, which is a new system operators and maintenance staff are then in a
technology not previously widely used in the power industry position to take further actions. The protective engineers
has been deployed only in the last decade and on a very start analyzing faults in more details. They visually inspect
limited scale [3]. recorded data and also check and compare IED records
before making a decision about nature of the fault and
The latest developments are an extension of the related equipment (protective relays and circuit breakers)
previous ideas but they explore two distinct directions: a) actions. In the case of permanent fault the maintenance
making the analysis more integrated across data from group is requested to go to the field, assess any damages,
different IEDs, and b) providing more elaborate tools for and fix the damage as needed. For this group it is extremely
viewing the original IED data and results of the analysis important to have information about precise location of the
using advanced computer graphics. This paper focuses on fault and surrounding circumstances such as terrain, type of
new solutions for graphical representation of recorded data supporting transmission line structures (towers) and
performance of the switching equipment (circuit breakers).
Knowing this information ahead of the time helps
maintenance crews preparing for the repair job and making
sure the job is completed efficiently so that the transmission
lines can be brought back to service as quickly as possible.
It can be seen from the above that proper data presentation,
ability to easily compare signals generated from IEDs and
good fault location presentation are important in trying to
minimize outage time.
The IEDs used to collect the data recordings in
substations considered in this paper are: digital protective
relays (DPRs), circuit breaker monitors (CBMs) and digital
fault recorders (DFRs). Those IEDs provide detailed
Figure 2. List of signals in CBM recordings
information about fault type, fault location, power quality
disturbance, operation of protective relays and operation of
DFR is a device with an ability to capture and store
circuit breakers.
short transient events, longer-term disturbances and trend of
input quantities such as RMS, frequency, harmonics, power
DPR is designed to calculate operating conditions on an
and power factor [10]. This device records huge amount of
electrical circuit and trip (open) circuit breakers when a
data. Figure 3 shows typical signals recorded by DFRs and
fault is found [6]. The DPRs respond to conditions like
used in the analysis.
sudden change in impedance, over-current or voltage,
reverse power flow, over- and under- frequency, and they
would trip for faults up to a certain distance away from a
substation but not beyond that point. The DPR records and
generates huge amount of data relevant for the analysis.
Figure 1 shows summary of data recorded and/or generated
by a typical DPR [7].
CBM is developed at Texas A&M University and main
purpose is to monitor circuit breaker (CB) condition on-line
[8]. CB is an automatically-operated electrical switch
designed to disconnect and hence protect an electrical
circuit (transmission line) from damage caused by overload
or short circuit [9]. Figure 2 shows list of the signals that are
recorded by CBM.
Figure 3. Input signals for DFR analysis application
Figure 4. Interconnection diagram of substation IEDs
Figure 1. Summary of data in DPR files and reports
the status and timing of that operand is validated. If not, a
failure or misoperation is identified and diagnosis is
initiated to trace the reasons by the logic of cause-effect
chain [13].
CBMA (Circuit Breaker Monitor Analysis) is an
application based on analysis of records of waveforms taken
from the circuit breaker control circuit using a Circuit
Breaker Monitor (CBM) device. It enables protection
engineers, maintenance crews and operators to quickly and
consistently evaluate circuit breaker performance identify
deficiencies and trace possible reasons for malfunctioning.
It can automatically analyse switching operations of large
Figure 5. AEA System architecture
number of circuit breakers under complex switching
conditions [14].
The developed system takes IED data as shown in
Figure 4 and supports client/server architecture shown in
Implementation architecture for each of the three
Figure 5. The part that resides on a PC in the substation
solutions is shown in Figures 6-8 respectively.
includes the Automated Event Analysis (AEA) Client which
interfaces to the CBM, DPR and DFR devices connected to
the Substation PC [11]. The server side resides at remote
location and consists of AEA Server software integrating
three automated analysis applications (CBMA, DPRA,
DFRA), database and web application.
3 DATA/INFORMATION FROM AUTOMATED
ANALYSIS APPLICATION
An IED alone typically may record an enormous
amount of data, but the case usually is that the output cannot
Figure 6. DFRA Architecture
sufficiently aid any utility personnel in making complete
interpretation of an event without information coming from
automated analysis of recorded data. To address the
different needs of different utility personnel, it is important
that the integrated substation data undergo further
processing to produce more useful and readable reports
containing information pertinent to the task at hand. Thus, a
few automated analysis applications were developed as
summarized below:
DFRA (Digital Fault Recorder Analysis) - provides
automated analysis of DFR event records. The analysis
looks at all the monitored circuits and identifies the one
with the most significant disturbance. For that selected
circuit, DFRA performs signal processing to identify pre-
Figure 7. DPRA Architecture
and post-fault analogue values, statuses of the digital
channels corresponding to relay trip, breaker auxiliary,
communication signals, etc. The expert system determines
fault type, faulted phases, checks and evaluates system
protection performance. At the end, the analysis program
calculates the fault location [12].
DPRA (Digital Protective Relay Analysis) - is an expert
system based analysis application which automates
validation and diagnosis of relay operation. Validation and
diagnosis of relay operation is based on comparison of
expected and actual relay behaviour in terms of the status
Figure 8. CBMA Architecture
and timing of logic operands. If actual status and timing of
an operand is consistent and as expected, the correctness of
To present data/information, there is a need for two
types of graphical user interfaces: the desktop and web user
interface. The desktop user interface, which is meant to
support local user connected to the computer at a substation
site, may be used by protection engineers. The developed
user interface provides advanced waveform viewer, which
will be further discussed in the next section. Also this
application can be used for testing purpose since it provides
ability to change device connections and settings. That
means that a new IED can be easily connected, configured
and tested using this interface. The interface allows
determining which data will be deleted and which archived
in the database. On the other hand, the web user interface
can be used by protection and maintenance groups, as well
as the system operators. It requires only a web browser
coupled with cell phone to be used to access data from the
field (substations) at remote site (control centre or staff
offices). This interface has ability to show physical Figure 9. Signal waveforms display
environment of faulted area, which will be discussed later.
The fault location can be shown in 2D and 3D view as will
be elaborated in the following section. This
data/information viewing approach makes it easier to assess
fault location accuracy and handle related tasks.
4 DATA/INFORMATION DISPLAYING
In the fault analysis process, several utility groups are
involved: operators are the first to make note of the fault,
then protection engineers are asked to perform detailed
analysis of causes and consequences, and maintenance
crews are sent to inspect and if needed repair damaged parts
of the system caused by a fault.
Before protection engineers make final decision
regarding the fault, they usually visually inspect generated Figure 10. DFR report
analysis reports and data recorded by IEDs (signal
waveforms). The inspection of signal waveforms can be
improved by a few additional functionalities allowing easy
manipulation and viewing. The visibility of each signal can
be enhanced by providing several graphycal display
features: selection of signals to be viewed including an
option to remove some signals from the dispaly, comparison
of signal waveforms by displaying them superimposed in
the same view with a color code, user ability to move a
displayed signal to any other view by dragging its label, and
signal zooming to view further details. The user should be
able to see in single view a time sequence of all the signals
that occured during the same event and got recorded by
IEDs. An example is shown in Figure 9.
The reports generated by IEDs are usually difficult to
interpret, as shown in Figure 10. Because of that, automated
Figure 11. Report for protection engineers
analysis applications are developed and implemented. As an
example of the analysis application for each IED, the
To improve presentation of data/information,
module that generates reports specialized only for
customized techniques may be combined with the standard
protection engineers is developed. Such automated analysis
ones typically used for data/information presentation in
report contains only essential information as shown in
other applications unrelated to power systems. Commercial
Figure11.
software for power system presentation may be combined
with automated analysis software to improve access and
make data/information presentation more user friendly and
understandable. For instance, the results of fault data
analysis that point out to the fault location in the electric
circuit representation of the power system network may be
combined with geographical and model data about the same
network producing more comprehensive views of the
troubled area. An example of using Power World
commercial software to represent power system network
and enhancing it with custom designed software to
accurately determine fault location is shown in Figure 12
[15]. The same results for fault location may be overlayed
on the earth satellite pictures obtained from Google Earth,
as shown Figure 13 [16]. This way, in case of outage it is Figure13. Satellite view of fault location area
easy not only to determine where the fault location may be
in the electrical network but also to know what to expect
from the physical terrain surrounding actual equipment
around fault location. This information is important for the
maintenance crews that are supposed to patrol the area,
locate the fault, assess possible damage from the fault, and
fix the problem. To give even better information about the
equipment and area characteristics, a 3D model of the
equipment and physical area may be developed as shown in
Figure 14. This model allows maintenance crews to view
the area from different angles allowing better assessment of
what may be involved in repairing transmission line
structures (towers), and what equipment and parts may be
needed to complete the job. This versatility of graphical
options for representing data/information associated with
field recordings, electrical networks, and physical outline of
the equipment is not available today and yet offers Figure 14. 3D view of fault location area
significant benefits to various utility groups.
5 CONCLUSION
Besides the examples shown in this paper, some
additional graphical views of the switching equipment are This paper introduced new concepts of utilization and
developed by the authors and reported earlier [17]. presentation of substation data/information. It emphasizes
the importance of good data/information presentation when
attempting to reduce outage time in power systems and
make the remedial process easier. The following are major
conclusions:
Desktop viewing of signal waveforms captured by
recording devices in substations allows utility personnel
to deal with test and evaluation tasks for individual
recording devices, which is very important to be able to
maintain and evaluate performance of the all-digital
monitoring solutions
Web browser viewing of recorded data and information
produced through automated analysis allows utility
personal located in control canter and/or other offices
remote from the substations to maintain timely
awareness of the critical events in power system such as
occurrence of faults
The graphical interfaces can significantly benefit from
Figure 12. Power world fault display
mixing the data/information derived from recorded
signals with other data such as satellite images of
certain geographical area or 2D and 3D views of
various power apparatus obtained from advanced Analysis of Circuit Breaker Operation, IEEE Transactions
equipment models. on Power Delivery, Vol. 20, No. 3, pp 1910-1918, July
2005.
6 ACKNOWLEDGMENT [15] Demo Software. Power World Corporation. ND. 4
Nov. 2007
The authors would like to thank the following /demosoftware.asp>.
organizations for funding the developments reported in this [16] Explore, Search and Discover. Google Earth. ND. 4
paper: EPRI (through TC agreement with CenterPoint Nov. 2007 .
Energy and HydroOne), PSerc and DOE-Current [17] M. Kezunovic, E. Akleman, M. Knezev, O. Gonen, S.
Technologies Corp. Special thanks are due to Mr. Don Natti," Optimized Fault Location", IREP Symposium 2007,
Sevcik from CenterPoint Energy for providing data to test Charleston, South Carolina, Aug 2007.
the various solutions mentioned in the paper.
7 REFERENCES
[1] Test Laboratories International, Inc. tli-inc.com. ND.
4 Nov. 2007
[2] McDonald, J.D.; Rajagopalan, S.; Waizenegger, J.R.;
Pardo, Realizing the Power of Data Marts
IEEE Power and Energy Magazine, Page(s): 57-66, May-
June, 2007
[3] M. Kezunovic, T. Popovic, "Substation Data Integration
for Automated Data Analysis Systems," IEEE PES General
Meeting, Tampa, Florida, June 2007.
[4] M. Kezunovic, C.C. Liu, J. McDonald, L.E. Smith,
Automated Fault Analysis, IEEE Tutorial, PES, 2000.
[5] M. Kezunovic, M. Knezev, "Temporal and Spatial
Requirements for Optimized Fault Location" Hawaii Intl.
Conference on System Sciences, HICCS-39, Hawaii,
January 2008.
[6] Relay. Wikipedia: The Free Encyclopaedia. 8 Nov.
2007 .
[7] X. Luo, M. Kezunovic, Automated Analysis of Digital
Relay Data Based on Expert System, PowerTech 2005
Conference, St. Petersburg, Russia, June 2005.
[8] M. Knezev, Z. Djekic, M. Kezunovic, Automated
Circuit Breaker Monitoring, IEEE PES General Meeting,
Tampa, Florida, USA, June 2007.
[9] Circuit breaker. Wikipedia: The Free Encyclopaedia.
6 Nov. 2007 .
[10] M.Kezunovic. Multiple Users of Substation Data-Final
Report. 2006. 4 Nov. 2007 .
[11] M. Kezunovic, G. Latisko, M. Knezev, T. Popovic,
Automation of Fault Analysis: Implementation Approaches
and Related Benefits, International Conference on
Electrical Engineering, ICEE 07, Hong Kong, July, 2007.
[12] M. Kezunovi, P. Spasojevi, C. Fromen, D. Sevcik,
An Expert System for Transmission Substation Event
Analysis, IEEE Transactions on Power Delivery, Vol. 8,
No. 4, pp 1942-1949, October 1993.
[13] X. Luo, M. Kezunovic, An Expert System for
Diagnosis of Digital Relay Operation, 13th Conference on
Intelligent Systems Application to Power Systems,
Washington DC, USA, November 2005.
[14] M. Kezunovi, Z. Ren, G. Lati ko, D.R. Sevcik, J.
Lucey, W. Cook, E. Koch, Automated Monitoring and