Published in Structure magazine November ****

Coming Up with Tie-downs

Wind Uplift Restraint Design Using Continuous Rod Tie-down Assemblies

By Bryan Wert, M.S., P.E., SECB, Branch Engineer for Simpson Strong-Tie

Continuous load path or complete load path are key phrases in engineering design established in IBC

sections 1604.9, 2304.9.6, and IRC section R301.1. These phrases require designers to detail

connections throughout the structure to resist and transfer overturning, sliding and uplift forces from their

point of origin down to the foundation. However, wind uplift restraint and load transfer may be negligible in

some conditions, or unfamiliar to many engineers.

Engineers designing structures with tile roof coverings in regions with 85 or 90 mph wind speeds may

have a general note or typical detail pertaining to uplift restraint on their plans. In these areas of the

country, heavy dead load often allows toenail fastening of roof framing to wall framing to restrain wind

uplift. That s it end of load path.

Conversely, engineers designing structures with lighter weight roof coverings, such as asphalt shingles, in

areas with relatively low 90 mph wind speeds must use hurricane ties to transfer uplift loads, ranging from

60 to almost 300 pounds per lineal foot (plf). Wall and floor dead loads reduce this force as it is

transferred down the structure, but typically connections are still needed to create the required continuous

load path all the way down to the foundation. This is especially true in high wind regions like the Gulf and

Atlantic coasts, Hawaii, and special wind regions in the Rockies and Pacific Northwest where design wind

speeds can reach up to 150 mph. Structures in these regions, depending on exposure category, may

experience extremely high uplift loads exceeding 1000 plf.

A New Load Path Solution

For decades metal connectors, such as hurricane ties, twist straps, flat straps and hold-downs, have been

used to resist uplift loads from the point of origin to the foundation, creating the uplift restraint load path in

light-framed construction. Real-world tested and proven; these connectors, their capacities, and their

installation methods are well understood by both designers and installers. Recently, rod systems have

been introduced to the light-framed construction industry as a seemingly simple means of creating a

continuous load path for resisting wind uplift forces.

When rod systems were first introduced, some likened all-thread rods spaced regularly every few stud

bays in wood construction to vertical rebar spaced regularly every few cells in CMU construction, equating

the wood double top plate to the block bond beam or concrete tie beam (see Figure 1). While it s fairly

simple to understand how these load paths work, this is where the similarities end. The capacity of a steel

reinforced bond beam or concrete tie beam clearly is much different than that of a wood top plate when

acting as an uplift load collector.

Simpson Strong-Tie Company Inc. 1 www.strongtie.com

Unfortunately, some may over

simplify the load path by

providing rod system layouts

that base the wind uplift rod

restraint spacing on rod tension

and bearing plate capacities

alone. This inadequate design

may lead to building damage,

structural system performance

problems, and ultimately life-

safety issues. Many other

factors need to be considered in

the design of a wind uplift rod

system, such as bending

capacity of wood top plates,

deflection limitations of wood

top plates, top plate rotation

issues, tension rod elongation

limitations, wood shrinkage

concerns and wood

compression under dead load.

Determining Uplift Load Paths

Unlike lateral forces from wind

or seismic loading which

transfer into the structure at the

roof and each floor diaphragm,

wind uplift typically loads the

structure solely at the roof

diaphragm. Uplift may be

calculated using ASCE 7 or pre-

calculated uplift values can be

found in either Table 2.2A of the

Wood Frame Construction

Manual (WFCM) or Table

2308.10.1 of the International

Figure 1: Load path comparison between CMU wall using

Building Code (IBC). Uplift

steel rebar and wood wall using steel all-thread rod.

reactions then may be provided

in engineering plans or in roof

truss calculations.

Once the uplift along each wall line of a building is determined and the appropriate hurricane ties to

transfer uplift from the roof framing to the top plate are chosen, what comes next? What are the

requirements to properly create a continuous load path using steel all-thread rod tie-down assemblies?

What governs rod spacing? To date, there doesn t exist a guide or a design standard that provides these

Simpson Strong-Tie Company Inc. 2 www.strongtie.com

steps for design. Consequently, designers are currently left with using engineering judgment based on

rational analysis to create this load path.

The Missing Link: Top Plate Considerations

Knowing rod tensile strength and wood bearing capacity are important, but they do not provide enough

information to complete the rod spacing layout. Designers must verify that top plate bending capacity

does not control the design of wind uplift rod systems by analyzing the flat wood plate bending (or flexural

forces) in the wood top plates. Unless specifically detailed for splice conditions, only one of the wood top

plate members should be considered to resist the uplift bending forces. To find the bending stress in the

top plate, designers can use the simple engineering equation: Fb = M/S, where M = moment (possibly

based on three equal span uniform loading) and S = section modulus (of the wood top plate). If the span

between rods is too great, top plate bending failure will control design. Testing has shown this wood top

plate flexural failure (see Figure 2).

Figure 2: Obvious top plate bending in

testing of rod system with 72 inch o.c.

spacing at the Simpson Strong-Tie

Tyrell Gilb Research Lab in Stockton,

California. Ultimate load is 290 plf;

using a factor of safety = 2.0, yields an

allowable uplift capacity of 145 plf.

Servicibility issues also must be

considered in rod spacing design. In

many cases deflection, not bending

strength, of the top plates may

actually govern the rod spacing

design. As the top plate bends, it is

deflecting between supports which

in this case, are rods. Of course in

extreme cases this could lead to structural system damage and possible failures, but consider the effect

of top plate deflection on wall and ceiling finishes. What deflection limit should be allowed in the top

plate? 1/8 inch? 1/4 inch? Should the limit be based on the span between rods, such as L/180 or L/240 as

suggested by REA, an engineering group in Florida that has been working with rod systems for several

years? At this point the judgment of the design professional and the requirements of the building owner

govern as this is not currently defined in the code.

Another important concern is top plate rotation due to eccentric loading. The uplift load path becomes

compromised if the top plate rotates. Uplift forces are generally transferred into the top plate through a

hurricane tie in high-wind areas. Hurricane ties are typically installed by attaching the rafter or truss to the

side of the top plate, and usually on the inside of a structure. If the next connection in the load path is in

the middle of or on the opposite side of the wall, the eccentricity created by the offset load path causes

the top plate to rotate, diminishing the amount of load the system is capable of transferring.

More than a decade ago, Clemson University completed a study on top plate roll showing this diminished

load transfer. While their findings were published in the Journal of Light Construction in 1996, this

Simpson Strong-Tie Company Inc. 3 www.strongtie.com

phenomenon which Clemson researchers dubbed top plate roll still is not widely known or understood.

Compared to an assembly with the rafter-to-top plate and top plate-to-stud connection on the inside of the

wall, an assembly with the rafter-to-top plate connector on the inside and sheathing on the outside as the

only plate to stud connection had nearly a 60% reduction in uplift capacity. The latter scenario creates an

uplift load path moment arm equal to the wall width forcing the top plate to roll when loaded.

In a rod system the bearing

plate transfers the load into the

steel rod roughly at the center of

the top plate width. This reduces

the uplift load path moment arm,

and thus reduces the eccentric

loading. However, testing has

shown that even this shorter

moment arm causes the top

plate to rotate before it is

capable of transferring the full

load into the rod system. The

test in Figure 3 shows rods at

48 inches on center and this top

plate roll phenomenon in action.

Figure 3: The distance between the hurricane tie and the rod restraint creates an eccentric loading

condition, causing top plate rotation and reducing the uplift load that the system is capable of transferring.

Figure 4: Sheathing and hurricane ties on opposing sides of the wall with rods at 48 inches o.c. Top plate

rotation is still unrestrained.

Pulling Double Duty What is

the Effect of Sheathing?

Can sheathing installed on the

opposite side of the wall from

the hurricane tie help to control

top plate roll by restraining the

side of the top plate? Uplift

testing did show that the wood

top plate s ability to transfer load

increased if the wall was

sheathed on one side. However,

Figure 4 shows this same

rotation action even with

sheathing attached to the

outside of the wall and hurricane

ties on the inside of the wall. Is

Simpson Strong-Tie Company Inc. 4 www.strongtie.com

this surprising? It shouldn t be considering why the sheathing is usually there for shear resistance, not

uplift. As a designer, if you count on that sheathing to help with uplift transfer, then the interaction effects

of uplift and shear must be considered in order to know how much the shear wall capacity will be

reduced.

Another design issue becomes evident in Figure 5, which shows that restraining the top plate on one side

with structural sheathing while uplift load is transferred into the top plate with a hurricane tie on the

opposite side can cause cross-grain tension failure in the top plate. The National Design Specification for

Wood Construction (NDS) states in section 3.8.2 that, Designs that induce tension stress perpendicular

to grain shall be avoided whenever possible. When tension stress perpendicular to grain cannot be

avoided, mechanical reinforcement sufficient to resist all such stresses shall be considered. Figure 6

shows that top plate rotation can be compensated for with the use of top plate-to-stud connectors so

much so in fact that the test can force extreme top plate failure and achieve a true ultimate load.

Figure 5: With rods centered in the wall and Figure 6: Simpson Strong-Tie TSP top plate-

sheathing on opposite side of wall, cross-grain to-stud connectors restrain the top plate

tension failure occurs as top plate bends upward. rotation, allowing the maximum load to be

Mechanical reinforcement is needed. transferred to the rod tie-down system.

This top plate rotation restraint also may be possible if the roof framing-to-top plate connections are made

on the outside of the wall, on the same side as structural sheathing. This allows the sheathing to resist

rotation, but it creates new design questions. Will sheathing be on every wall? If not, what detailing is

required for both sheathed and un-sheathed wall conditions? If hurricane ties attach the roof framing to

the top plates and sheathing is fastened over them, what installation and inspection issues arise? Do

hurricane ties have similar capacities installed over sheathing? And again, by relying on sheathing for

uplift resistance it s likely to reduce shear capacity which is usually the primary purpose for structural

sheathing.

Wood Shrinkage Leads to a Less Effective System

At the top of a continuous rod tie-down system, uplift will not transfer into the rod unless a nut is tight

against the bearing plate. As moisture escapes from wood framing the wood begins to shrink. Coupling

wood shrinkage with compression due to dead load causes the bearing plate to shrink away from the

nut s fixed position on the all-thread rod. The gap between the nut and the bearing plate requires

additional deflection to occur prior to the system being engaged in a wind event. Figure 7 shows a

Simpson Strong-Tie Company Inc. 5 www.strongtie.com

substantial gap between the nut and bearing plate in a wind uplift restraint rod system at a project in

Orlando, Florida. This is the only point of restraint in wind uplift rod tie-down systems and hence the only

location for the gap to occur when wood shrinks and the steel rod does not.

Even though most manufacturers

recommend that contractors go

back and tighten all the nuts down

to the bearing plates prior to closing

up the wall and ceiling assembly, it

can be assumed this doesn t always

happen. Furthermore, shrinkage

and dead load compression may

continue to occur through the first

six months to one year of the life of

the structure. Take-up devices will

keep rod tie-down systems

continuously engaged,

compensating for wood shrinkage

and compression. Without a take-up

device, gaps are likely to occur in

rod systems and will reduce the

system s effectiveness and

performance.

Figure 7: What was once a nut tightly secured to the bearing plate, now has a gap as wood shrinkage and

dead compression occur throughout the structure.

That s Stretching it: Steel Rod Elongation

Another important consideration is steel rod elongation. The elongation or stretch of a steel rod is

calculated with a simple equation, = PL/AE, dependant on the tensile force (P), rod length (L), effective

cross-sectional area (A), and modulus of elasticity (E) which is 29,000,000psi for all structural steel. From

this equation it is easily surmised that the higher the tensile (uplift) force, the longer the rod, or the smaller

the rod diameter, the greater the elongation. For example, in a four-story, 40-foot tall structure, a -inch

diameter rod with a tensile capacity of roughly 1100 lbs. would stretch more than half an inch, which is

obviously not the best solution if this is your wind uplift restraint system. The more elongation that occurs

in the rod, the more deflection that will occur in the structure under uplift loading. Consequently it makes

sense to limit elongation, but again this limit is another issue that falls on the shoulders of the designer as

there are no current code limitations.

The Bigger Picture

The uplift-force resisting system is only one of the force resisting systems in a structure. Lateral-force

resisting and gravity-force resisting systems are also required. In wood construction, beams, joists, plates,

and studs may initially be sized to resist gravity loads. Lateral loads, however, require reevaluation of

wood members and the addition of steel fasteners, connectors, and anchors to create a properly

designed continuous load path. Markedly different from the single point of origin for uplift forces, lateral

forces are introduced into the structure at multiple points of origin. Diaphragms at the roof and each floor

Simpson Strong-Tie Company Inc. 6 www.strongtie.com

level distribute these forces; and in wood construction shear walls typically continue the load path to the

foundation.

The architect s layout of door and window openings and the engineer s choice of shear wall locations,

shear wall lengths, sheathing materials, end stud/post size, and overturning restraint hardware greatly

affect the overturning forces in a structure. The rod sizes in wind uplift tie-down systems are generally too

small to resist the higher uplift forces generated by cumulative shearwall overturning in multi-story

structures, so higher capacity holdown solutions are required at the ends of shearwalls. Accordingly, uplift

resisting and lateral-force resisting systems should usually be designed as two distinct systems. If not, the

effects of combined loading must be considered for example when using a steel rod to resist wind uplift

and lateral force induced shear wall overturning to properly design components of these systems.

Design with the Public in Mind

Buildings are going up every month with continuous rod tie-down assemblies used as the structural

system for uplift restraint. Unfortunately not all of these systems are designed correctly. Designs often

forego important constraints of wood top plate bending capacity, wood top plate deflection, wood top plate

rotation, wood shrinkage, wood compression under dead load, and tensile steel rod elongation. Worse

yet, some designs compound these errors by relying on rods designed solely for uplift for lateral

overturning as well without proper consideration given to the effects of load interaction. It s up to the

designers and professional engineers that seal continuous rod tie-down uplift restraint assemblies to

ensure these design factors are taken into consideration in order to protect the life safety of the public.

This task is not necessarily easy, especially without a code approved design guide or standard to follow.

Engineers will have to interpret the existing information from rod system manufacturers and use their

experience and judgment to create robust, economical, and most importantly, safe continuous rod tie-

down uplift restraint systems.