Post Job Free
Sign in

Maintenance Power

Location:
Ames, IA
Posted:
November 12, 2012

Contact this candidate

Resume:

*th International Conference on Probabilistic Methods Applied to Power Systems, Iowa State University, Ames, Iowa,

September 12-16, 2004

Circuit Breaker and Transformer Inspection and

Maintenance: Probabilistic Models

Satish Natti, Panida Jirutitijaroen, Mladen Kezunovic, Fellow, IEEE, and Chanan Singh, Fellow, IEEE

out. Finally, a circuit breaker maintenance model is proposed.

Oil filled and air blast circuit breakers are considered in this

Abstract Circuit Breakers and Transformers are two of the

most common components in the power system. Catastrophic paper since most of the circuit breakers that are already in

failure of these components will result in high cost associated service are of the above type.

with the loss of load and component replacement. Preventive

maintenance may reduce these costs by extending the

II. DETERIORATION PROCESSES OF CIRCUIT BREAKER

components lifetime and increasing availability. However, too

much maintenance may be costly while too little maintenance

A. Deterioration of Operating Mechanism

may result in catastrophic failure. Probabilistic models that will

include the effects of maintenance on reliability are needed to This includes the deterioration of interrupter chamber,

perform cost benefit analysis and arrive at an optimal valves and various moving components. Moisture and

maintenance strategy.

corrosion of metal parts are some of the causes that are

A probabilistic maintenance model introduced earlier for

responsible for deterioration process of operating mechanism.

power transformer is proposed for circuit breaker uses in this

As a result, the breaker may fail to operate.

paper. The model is based on data coming from a study of

deterioration process, maintenance tasks, and inspection tests for

B. Deterioration of Contacts

circuit breaker.

Oxidation of contacts results in formation of a thin oxide

Index Terms Circuit Breakers, transformers, inspection,

film over the contact surfaces. At higher temperatures these

maintenance, probabilistic model.

oxide materials will begin to soften and might result in a

plastic deformation. Finally, contact erosion takes place due to

I. INTRODUCTION

the vaporization of electrodes during the current interruption

F AILURE of circuit breakers and power transformers can process [4]. These conditions may result in binding of

greatly affects the power delivery. The remaining life of contacts.

power apparatus and maintenance cost are two most important

C. Deterioration of Oil

aspects, which affects the maintenance policies. Various

maintenance strategies are reported in literature so far [1]. It Arc byproducts combine with moisture and oxygen in the

was concluded that power apparatus service availability and oil and reduce the dielectric strength of the oil. Accumulation

replacement cost should be balanced in order to get an optimal of these products contributes to the deterioration of oil [5]. If

maintenance strategy. Incipient failures have along term- prolonged, this condition causes arcing in the insulation

accumulated effect, which may cause major failures if no gradually developing into an internal fault.

related maintenance action is taken. In reference [2], failure,

D. Deterioration Failure

repair and maintenance sequences are described as Markov

Deterioration process results in deterioration failure, which

processes and optimal maintenance intervals are discussed in

is a long term-accumulated fault. It can happen mostly due to

detail. Based on this concept, a maintenance model for

deterioration of contacts and oil, and break down of insulating

transformer is presented in [3].

materials such as bushings etc. [5, 6].

In this paper, a similar idea is applied to circuit breakers. In

order to build the probabilistic model for estimating circuit

III. MAINTENANCE ACTIONS

breaker failure rate, the deterioration process, inspection tests,

and maintenance actions are discussed. Then, a comparison Various maintenance actions for power circuit breakers are

between circuit breakers and transformers regarding operating summarized in reference [7]. In the proposed model, two

conditions, inspection tests and maintenance actions is carried different levels of maintenance actions are considered.

A. Basic Maintenance

This work was supported by Pserc project, Automated Integration of

1) Operating Mechanism

Condition Monitoring with an Optimized Maintenance Scheduler for Circuit

Clean all insulating parts from dust and smoke

Breakers and Power Transformers, and in part by Texas A&M University.

Satish Natti, Panida Jirutitijaroen, Mladen Kezunovic and Chanan Singh Clean and lubricate operating mechanism and apply

are with the Department of Electrical Engineering, Texas A&M University,

suitable grease for the wearing surfaces of cams,

College Station, TX 77843-3128 USA (e-mails: ******@**.****.***,

rollers, bearings etc.

****@****.***, *******@**.****.***, *****@**.****.***).

Copyright Iowa State University, 2004

processing techniques. The time-axes of reference frequency

Adjust breaker-operating mechanism as described in

pattern and test frequency pattern are aligned to indicate any

the manufacturer s instruction book.

changes in the condition of the operating mechanism. The

Make sure all bolts, nuts, washers, cotter pins etc. are

presence of an abnormal event in the test signature will change

properly tightened.

the frequency, and the time at which this event occurs.

After servicing the circuit breaker, verify whether the

3) Control Circuit Monitoring

contacts can move to the fully opened and fully closed

Portable test sets are generally used to monitor the control

positions or not.

circuit. The circuit breaker is forced into operation and the

2) Contacts

control circuit signals are recorded [11]. The following are the

Check the alignment and condition of the contacts and

typical control circuit signals that can be monitored in practice

make adjustments according to the manufacturer s

[12].

instruction book

Trip coil current

Check if the contact wear and travel time meet

Close coil current

specifications

DC Supply voltage

3) Insulating Medium and Arc Extinction

A, B auxiliary contacts

Check for leaks and remove any water content. Check

X & Y Coils

governor and compressor for required pressure

Trip initiation

Recondition oil by filtering

Close initiation

B. Replacement

B. Contacts

This includes the replacement of various components.

Inspections related to circuit breaker contacts are mentioned

Arc chute and nozzle parts if damaged

in this section.

Governors and compressors if worn or malfunctioning

1) Contact Resistance Test

Contacts if badly worn or burned

The resistance of the main contact can be measured with a

Oil if dielectric strength drops below an allowable limit

portable double bridge (Kelvin) or a Ducter [7]. A DC current

and if any arc products are found in the oil.

is injected in one phase of the breaker, and the breaker is forced

into operation. The current and voltage over the contact are

IV. INSPECTION TESTS

measured and the dynamic resistance curve is calculated. The

This section gives an idea about how various inspections can condition of the contacts can be analyzed by comparing the

be done, and what is the information that can be obtained from measured resistance curve with previous measurements [9].

those tests. Some of the possible inspection tests used in practice 2) Contact Temperature Monitoring

for a circuit breaker are mentioned below [8]. The inspection Large changes in contact temperature may be due to broken

tests are grouped according to the order of components that are contact fingers, excessive burning of the main contacts, material

discussed in section II. degradation, oxide formation, weak contact springs, improperly

or not fully closed contacts etc. Optical sensors are used to

A. Operating Mechanism

measure the temperature of the contacts [4].

Inspection tests, which give the performance of operating

C. Inspection of oil

mechanism either directly or indirectly, are presented in this

section. Oil sample can be taken and tested for its dielectric strength.

1) Contact Travel Time Measurement The following are the inspections that can be done in practice

The motion of the breaker contacts can be determined with [5].

contact travel time measurement. It is a plot of position Color and visual inspection

(distance) of contacts with respect to contact travel time, and Interfacial tension (soluble contaminants measurement)

can be obtained by a resistive transducer [9]. The transducer is Dissipation factor (measure of power lost as heat)

usually mounted on a moving part of the breaker. The contact

D. Partial Discharge

travel time measurements provide information about the

operating components of the circuit breaker, which include Insulation failures of circuit breakers can be detected by

mechanical links and interrupter contacts. Partial discharge monitoring [13]. The test procedure and

2) Vibration Analysis equipment for the partial discharge monitoring are discussed in

Mechanical malfunctions, excessive contact wears, detail in reference [14]. Various methods are reported in

maladjustments, other irregularities and failures can be detected literature so far but the cost varies according to the test

through vibration patterns [10]. Accelerometers mounted procedures and accuracy of results.

usually on the arcing chamber and operating mechanism, are

used to record the vibrations. The recorded vibration patterns

are converted into time/frequency patterns using signal-

V. COMPARISON BETWEEN A CIRCUIT BREAKER AND D2

D1 D3 Fail

TRANSFORMER

Circuit breaker is an electrical device that operates on Inspection test Inspection test Inspection test

command. Once the operating mechanism receives trip or close

signal from a control circuit, it starts working and opens or Investigation Investigation Investigation

process process process

closes the main contacts respectively. The overall performance

of the breaker depends on the operating mechanism, which C1 C2 C3 C1 C2 C3 C1 C2 C3

consists of various moving parts. Transformer is a device, D1 D1 D1

Basic Maint. Basic Maint. Basic Maint.

which while in service, is always in an energized state. The D2 D2 D2

D1 D1 D1

insulating oil properties used in breaker and transformer are D3 D3 D3

D2 D2 D2

different. Suggested limits for service-aged insulating oils for

D3 D3 D3

both breaker and transformer are given in table I [5]. Having an

idea about the similarities and differences between the two Replacement

Replacement Replacement

devices, and knowing the maintenance model of the transformer D1 D1 D1

Basic Maint. Basic Maint. Basic Maint.

will help in developing the maintenance model for the circuit D2 D2 D2

D1 D1 D1

breaker. Table II provides a comparison between the breaker D3 D3 D3

D2 D2 D2

and transformer characteristics.

D3 D3 D3

VI. PROPOSED MAINTENANCE MODEL AND DESCRIPTION Replacement Replacement Replacement

D1 D1 D1

A probabilistic model, based on the concept of representing

the deterioration process by various stages [3, 15] is shown in D2 D2 D2

Figure 1. Three deterioration stages i.e., the initial stage (D1), D3 D3 D3

minor (D2) and, major (D3) deterioration stages, followed by a

Fig 1. Proposed circuit breaker probabilistic maintenance model.

failure stage are considered. Inspection test is implemented at

each stage and the collected data is investigated to determine the

The model takes results from various inspection and

condition of the breaker. In this model, three different levels of

maintenance tasks and the frequency of performing the tasks as

breaker condition are defined: C1- satisfactory and no

inputs and gives the failure rates as output. The changes in the

maintenance is needed, C2- indication of abnormality or caution

mean time to failure indicator can be observed by considering

stage, needs further investigation or related maintenance and

different inspection and maintenance actions. This model can

C3- Failure stage or poor condition, needs replacement. Further,

help in obtaining optimum maintenance intervals such that both

the maintenance process is divided into three levels; (1) Do

the component availability and the total cost are balanced.

nothing, (2) Basic maintenance, and (3) Replacement. Once the

Various inspection tests and maintenance actions considered in

suggested maintenance action is taken, the subsequent condition

the model are discussed next.

of the breaker is determined.

A. Inspection Tests

The following inspection tests are considered in developing

TABLE I

SUGGESTED LIMITS FOR SERVICE-AGED OILS FOR TRANSFORMERS AND CIRCUIT

the proposed model. Air blast and oil circuit breakers are

BREAKERS [5]

considered in this study.

Test and method Transformer Circuit

1) Contact Travel Time Measurement

(Value for voltage class) Breaker

Condition of the circuit breaker can be obtained by

69 kV 69 230 230 kV Suggested

and kV and limit comparing the test curve with the reference curve. Figure 2

below above

shows various contact travel curves during the opening of a

Dielectric strengtha

circuit breaker [4]. The solid lines indicate the reference curve

KV minimum

and the dotted lines indicate the current observation. The

1 mm gap* 23 28 30 20

2 mm gap* 40 47 50 27 following are the possible observations from the Figure 2.

Contact separation occurred sooner than before:

Dissipation factora

contact wear

(power factor),

25 oC, % maximum 0.5 0.5 0.5 1.0 Faster circuit breaker stroke: kinetic energy of the

100 oC, % maximum 5.0 5.0 5.0 -

mechanism is above its upper limit

No damping at the end of the operation: shock

Interfacial tension, 25 30 32 25

mN/m minimum absorber failure

Reduction in total travel distance: binding or

a

Older transformers with inadequate oil preservation systems or

stalling of the mechanism or insufficient stored

maintenance, may have lower values

* *Alternative measurements of 0.04 in and 0.08 in respectively for gaps driving energy

The proposed criterion for assessment of the condition of Condition 3: excessive wear and need complete overhaul

operating mechanism is or replacement

Condition 1: satisfactory, test results follow the reference curve 2) Control Circuit Monitoring

Condition 2: caution stage, test results deviate slightly and need The recorded control signals are analyzed to find any

more attention abnormalities in the breaker operation. A detailed analysis of

circuit breaker operations based on automated monitoring of

control circuit is discussed in reference [12]. Table III shows

some of the possible causes for the behavior of the measured

signals [16].

Figures 3, 4, 5 and 6 show the sluggish trip latch, defective

close coil, defective auxiliary switch and defective battery

respectively.

The proposed criterion for the condition of control circuit is

Fig. 2 Comparison of circuit breaker contact travel curves [4]

Condition 1: within specification and will not require

maintenance

TABLE II

COMPARISON BETWEEN CIRCUIT BREAKER AND TRANSFORMER

Comparison Aspect Circuit breakers Transformers

Main components Contacts, interrupter, insulating medium, Winding, Cooling agent (for example, oil,

control circuit, mechanism which includes gas, or air), Bushing, Tap changer

cam, latches, springs, bearings, coils,

compressors, charging motors etc.

Operating Stored energy in springs or gas pressure is Transforms voltage from one level to another

mechanism used to move operating mechanism which preserving the same voltage frequency.

either opens or closes the main contacts

Deterioration Operating mechanism, oxidation of contacts Insulation paper in the winding, oxidation of

process and oil oil.

Particles produced Oxides, arc byproducts such as carbon, water, Sludge, Water, Fiber, Gases (CO, CO2, etc.),

by aging process partial discharge Furfural, Partial Discharge

Failure Modes Fails to open on command Thermal related faults

Fails to close on command Dielectric related faults

Fails to conduct continuous or momentary Mechanical related faults

current (while already in use) General degradation related faults

Fails to maintain the insulation

Fails to contain insulating medium

Fails to indicate condition or position

Fails to provide for safety in operation

Inspection tests Contact travel time measurement Routine oil sampling test; dielectric

strength, resistivity, acidity, moisture

Vibration Analysis

content.

Control circuit monitoring

Dissolved gas analysis

Contact Resistance Test

Furfural analysis

Contact temperature monitoring

Partial discharge monitoring

Dielectric strength

Partial Discharge

Maintenance (For oil-immersed transformer)

Basic maintenance: lubricating mechanism

Oil filtering (online/offline)

components, check for compressor pressure

and dielectric strength of oil, adjusting all Oil replacement

components and contacts as per

manufacturer s instructions, check for

control circuit connections

Replacement of contacts, interrupters, oil,

damaged nozzles, springs, coils etc.

Condition 2: caution stage; need more attention TABLE IV

SUGGESTED LIMITS FOR CONTINUED USE OF SERVICE-AGED CIRCUIT

Condition 3: final stage; need major replacement

BREAKER INSULATING OIL [5]

Test and method Suggested limit

TABLE III

Dielectric strength 25

ABNORMAL WAVE FORMS [16]

kV minimum

Signal Name Signal Behavior Figure Possible Cause

Trip Coil Current Dip delayed Fig. 3 Binding or friction Dielectric strength, kV minimum

Close Coil Excessive noise Fig. 4 Defective close coil 1 mm gap* 20

current (distortion) 2 mm gap* 27

A&B Contacts Abnormal noise Fig. 5 Defective auxiliary

on contacts switch Dissipation factor (power factor),

DC Voltages DC Voltage Fig. 6 Defective substation 25 oC, % maximum 1.0

unstable battery or high

impedance short Interfacial tension, mN/m minimum 25

Color, ASTM units, maximum 2.0

*Alternative measurements of 0.04 in and 0.08 in respectively for gaps

Condition 1: satisfactory

Condition 2: should be reconditioned for further use

Condition 3: poor condition; dispose

Suggested limits for oil in condition 1 are listed in table IV.

Fig. 3. Trip current dip delayed Criterion for recondition is excessive carbon in oil and

reduced dielectric strength (dielectric strength drops below the

accepted limit).

A detailed analysis of inspection tests and the collected data

is needed for implementation of the model, and will be

included in further work.

B. Investigation Process

Information out of the inspection tests can be used to

Fig. 4. Close current excessive noise

determine the condition of the device followed by the

necessary maintenance action and rate of the next inspection.

C. Maintenance Action

1) Do nothing

The breaker is in satisfactory condition and no maintenance

Fig. 5. Noisy transition when opening is needed. The probability that the system is set back to same

stage is relatively high.

2) Basic Maintenance

This maintenance action increases the probability of going

back to the previous stage.

3) Replacement

Replacement of damaged components brings the system

Fig. 6. DC Voltage unstable

back to its original stage i.e. beginning stage.

3) Contact Resistance Measurement

The possible causes for abnormal increase in contact

VII. CONCLUSION

resistance are deposition of foreign material in contacts, loose

A probabilistic maintenance model for circuit breakers is

contacts and loose bushing connections [7].

introduced. Information collected during inspection tests is

The proposed criterion for the condition of contacts is

analyzed and the condition of the breaker can be defined.

Condition 1: satisfactory

Maintenance action is taken according to the condition of the

Condition 2: caution stage; need more attention

breaker. Implementation of the model using Monte Carlo

Condition 3: excessive wear and need complete overhaul

simulation is in progress. Maintenance cost and time to failure

4) Inspection of Oil

of each transformer and circuit breaker will be incorporated.

Service-aged oils are classified into the following three

conditions [5].

REFERENCES

[1] IEEE/PES Task Force on Impact of Maintenance Strategy on Reliability

of the Reliability, Risk and Probability Applications Subcommittee,

The present status of maintenance strategies and the impact of

maintenance on reliability, IEEE Trans. Power Systems, vol. 16, no. 4,

pp. 638- 646, November 2001.

[2] J. Endrenyi, and S. H. Sim, Availability optimization for continuously

operating equipment with maintenance and repair, in Proceedings of the

Second PMAPS Symposium, September 1988, Nov. 1989, EPRI

Publication EL-6555.

[3] Panida. Jirutitijaroen, and Chanan Singh, Oil-immersed transformer

inspection and maintenance: Probabilistic models, North American

Power Symposium, 2003, (NAPS 2003), October 2003.

[4] R. D. Garzon, High Voltage Circuit Breakers: Design and Applications,

2nd ed. New York: Marcel Dekker, 2002.

[5] IEEE Guide for Acceptance and Maintenance of Insulating Oil in

Equipment, IEEE standard C57.106-2002, November 2002.

[6] IEEE Guide for Diagnostics and Failure Investigation of Power Circuit

Breakers, IEEE standard C37.10-1995, December 1995.

[7] Maintenance of Power Circuit Breakers, Facilities Instructions,

Standards and Techniques vol. 3-16. [Online]. Available:

http://www.usbr.gov/power/data/fist/fist3_16/3_16_con.htm

[8] IEEE Guide for the Selection of Monitoring for Circuit Breakers, IEEE

standard C37.10.1-2000, December 2000.

[9] Martin H. B. de Grijp, Joost S. Bedet, Richard A Hopkins, and Jhon E

Greyling, Condition monitoring of high voltage circuit reakers

AFRICON, 1996, IEEE AFRICON 4th, vol. 2, 24-27 Sept. 1996, pp.

880-885.

[10] M. Runde, G. E. Ottesen, B. Skyberg, and M. Ohlen, Vibration analysis

for diagnostic testing of circuit-breakers, IEEE Trans. Power Delivery,

vol. 11, no. 4, pp. 1816-1823, October 1996.

[11] RTR-84 Circuit Breaker Response Recorder, Hathaway Systems

Corporation, Belfast, Ireland.

[12] M. Kezunovic, Z. Ren, G. Latisko, D. R. Sevcik, J. Lucey, W. Cook, E.

Koch, Automated monitoring and analysis of circuit breaker

operations, IEEE Trans. Power Delivery (Accepted, In Press).

[13] K. Goto, T. Sakakibara, I. Kamata, and S. Ikeda, On-line monitoring

and diagnostics of gas circuit breakers, IEEE Trans. Power Delivery,

vol. 4, no. 1, pp. 375-381, January 1989.

[14] IEEE Guide for Partial Discharge Measurement in Power Swithgear,

IEEE standard 1291-1993, June 1993.

[15] J. Endrenyi, G. J. Anders, and A. M. Leite da Silva, Probabilistic

evaluation of the effect of maintenance on reliability- An application,

IEEE Trans. Power System, vol. 13, no. 2, pp. 576-583, May 1998.

[16] Christopher Donald Nail, Automated Circuit Breaker Analysis, M.Sc.

Thesis, Dept. Elect. Eng., Texas A&M University, College Station, TX,

2002.

Copyright Iowa State University, 2004



Contact this candidate